Anybus X-gateway – DeviceNet Adapter - FIPIO Slave

The Anybus X-gateway allows you to seamlessly inter-connect PLC control systems and their connected devices between DeviceNet and FIPIO networks.

FAST COPYING OF I/O DATA

The X-gateways primary function is with the fast transfer of cyclic I/O data between the two networks. This offloads your PLC from working with additional calculations. The gateway acts as an Adapter/Slave on both networks. The data transmission is completely transparent with a maximum data capacity of 512 bytes in each direction.

EASY CONFIGURATION - NO PROGRAMMING REQUIRED!

The connection between the two networks is quickly set up in the Anybus Configuration Manager software, included with the X-gateway. No programming skills are needed to set up the X-gateway. As factory default the X-gateways have a pre-defined I/O size of 20 bytes I/O.

x-gateway-devs-fips

Features and benefits

  • Fast copying of cyclic I/O data between two networks (10-15 ms)
  • Proven and tested with all PLC manufacturers
  • Supports up to a maximum of 512 bytes of Input and Output data in each direction
  • Optional control and status information added to the I/O data for diagnostic purposes
  • Robust stand-alone housing for use in harsh industrial environments
  • Global free technical support and consultancy

DeviceNet Adapter features

DeviceNet Adapter settings can be made either via on-board switches, or by importing the provided .EDS file into engineering tool of the controlling PLC.

  • DeviceNet CONFORMANCE TESTED™ by ODVA
  • DeviceNetNet Specification version: Communications Adapter profile 12
  • Max. 512 bytes of Input and 512 bytes of Output data
  • DeviceNet baudrate 125, 250, 500 kbit/s
  • Supports I/O Slave messaging: Bit strobe, Polling, Cyclic, COS and Explicit Messaging
  • MacID node address setting via DIP switch
  • DeviceNet network configuration via .EDS file
  • 1x 5-pin, 5.08 Phoenix plug connector

FIPIO Slave Interface

FIPIO Slave settings are made by on-board rotary switches

  • Complete FIPIO functionality according to EN 50170
  • FIPIO Extended Device Profile (FEDP), Class 01 0
  • Max. 64 bytes (32 words) of Input and 64 bytes (32 words) of Output data
  • FIPIO baudrate 1 Mbit/s
  • FIPIO station address setting via rotary switches
  • 1x D-sub 9-pin male network connector

TECHNICAL SPECIFICATIONS

Dimensions (L•W•H)   114 x 44 x 127mm or 4,49 x 1,73 x 5,00"
Weight 400g or 0,880 lbs
Operating temperature -25 to +65 °C  or  -13 to +149 °F 
Storage temperature -40 to +85 °C  or  -40 to +185 °F 
Power supply 24 VDC +/- 20% via 2-pole 5.08 mm Phoenix pluggable screw connector  
Current consumption     max. 400mA (Typical 200mA)
Enclosure material  Aluminium and plastic
Installation position Vertical / Flat*
Galvanic isolation YES, on both BUS/Ethernet side
Mechanical rating IP20, NEMA rating 1
Mounting DIN-rail (EN 50022 standard)
I/O configuration via USB port with Anybus Configuration Manager software
Certifications CE, CULUSRoHS

Ordering information

Order Code  AB7856
Included components            

Gateway
Quick start documentation
USB configuration cable

Power supply not included

Configuration server software is available for download.

3 year guarantee. For purchasing instructions and terms and conditions, see: How to buy

    Related products

What you can do!

Connect any two industrial networks — Fieldbus, or Industrial Ethernet or connect to IT systems via MQTT or OPC UA.

Data exchange

Learn more about how the X-gateway exchanges I/O Data.

X-gateway assistance

Through HMS Technical Services, start-up assistance, on-site help and trainings are available.

Anybus X-gateway case studies

Click the button down below to read more about our case studies.