Anybus X-gateway – Modbus Plus Slave - PROFINET-IO Device

The Anybus X-gateway allows you to seamlessly inter-connect PLC control systems and their connected devices between Modbus Plus and PROFINET networks.

FAST COPYING OF I/O DATA

The X-gateways primary function is with the fast transfer of cyclic I/O data between the two networks. This offloads your PLC from working with additional calculations. The gateway acts as an Slave/Device on both networks. The data transmission is completely transparent with a maximum data capacity of 512 bytes in each direction.

EASY CONFIGURATION - NO PROGRAMMING REQUIRED!

The connection between the two networks is quickly set up in the Anybus Configuration Manager software, included with the X-gateway. No programming skills are needed to set up the X-gateway. As factory default the X-gateways have a pre-defined I/O size of 20 bytes I/O.

x-gateway-prts-mbps

Features and benefits

  • Fast copying of cyclic I/O data between the two networks (10-15 ms)
  • Proven and tested with all PLC manufacturers
  • Supports up to a maximum of 512 bytes of Input and Output data in each direction
  • Possibility to build web pages displaying and controlling a factory floor process with data from the other connected network
  • Fast, dynamic transfer of fieldbus data to e.g. SCADA/HMI/Enterprise level systems based on Microsoft Windows, via the included Anybus OPC server
  • Optional control status information added to I/O data for diagnostic purposes
  • Robust stand-alone housing for use in harsh industrial environments
  • Global free technical support and consultancy

Modbus Plus Slave Interface 

Modbus Plus address settings made via on-board DIP switches

  • Complete Modbus Plus slave functionality
  • Up to 32 words of global (cyclic I/O) data in each direction
  • Global Data Base Transaction, Point-to-Point commands, Read holding registers, Preset single register
  • Point-to-point parameter data (up to 125 words)
  • Onboard Node ID and Source ID switches
  • Modbus Plus baudrate 1 Mbit/s
  • 1x D-sub 9-pin female network connector

PROFINET I/O Device/Slave interface 

PROFINET IO Device/Slave settings can be made by importing the provided .GSDML file into engineering tool of the controlling PLC. 

  • Complete PROFINET-IO Soft-Real-Time (RT) communication
  • Max 512 bytes of Input and 512 bytes of Output data
  • Up to 64 slots / 1 sub slot
  • Cyclic data exchange (10 ms cycle time)
  • Acyclic Data exchange (Record Data Requests) 
  • Baud rate 100 Mbit/s
  • Integrated FTP server provides easy file management using standard FTP clients
  • Web server with dynamic data capability and Server Side Include (SSI) capability
  • Email client with dynamic data capability and Event-triggered email handling
  • TCP/IP Configuration via DCP (Discovery and Configuration Protocol)
  • PROFINET uplink configuration via web interface or .GSDML file
  • 1x RJ45 network connector

Technical specifications

Dimensions(L•W•H) 114 x 44 x 127mm or 4,49 x 1,73 x 5,00"
Weight 400g or 0,880 lbs
Operating temperature -25 to +65 °Cor-13 to +149 °F
Storage temperature -40 to +85 °Cor-40 to +185 °F
Power supply 24 VDC +/- 20% via 2-pole 5.08 mm Phoenix pluggable screw connector
Current consumption max. 400mA (Typical 200mA)
Enclosure material Aluminium and plastic
Installation position Vertical / Flat*
Galvanic isolation YES, on both BUS/Ethernet side
Mechanical rating IP20, NEMA rating 1
Mounting DIN-rail (EN 50022 standard)
I/O configuration via USB port withAnybus Configuration Manager software
Certifications CE,CULUS,RoHS

Ordering information

Order Code  AB7660
Included components                      

Gateway
Quick start documentation
USB configuration cable

Power supply not included

Configuration and Anybus OPC server 
software is available for download.

3 year guarantee. For purchasing instructions and terms and conditions, see: How to buy

Sales request: Contact

    Related products

Ce que vous pouvez faire !

Connectez deux réseaux industriels - Fieldbus ou Ethernet industriel - via MQTT ou OPC UA.

Échange de données

En savoir plus sur comment la passerelle X-Gateway échange les données d'E/S.

Assistance X-Gateway

Via les services techniques de HMS, assistance au démarrage, aide sur site et cours de formation sont disponibles.

Anybus X-Gateway: Rapports des utilisateurs

Découvrez dans nos rapports d'utilisateurs la versatilité de nos passerelles X.